function [FT,pp,Trm_loss,MVA_line] = find_cost_final(p);
Lf_ieee30bus_bygauss1;
%Power generator
busdata(2,7)=p(1);
busdata(5,7)=p(2);
busdata(8,7)=p(3);
busdata(11,7)=p(4);
busdata(13,7)=p(5);
%Voltage of Gen
busdata(1,3)=p(6);
busdata(2,3)=p(7);
busdata(5,3)=p(8);
busdata(8,3)=p(9);
busdata(11,3)=p(10);
busdata(13,3)=p(11);
%Transformer Tap
linedata(11,6)=p(12);
linedata(12,6)=p(13);
linedata(15,6)=p(14);
linedata(36,6)=p(15);
%load flow
Lfybus; % form the bus admittance matrix
ss=3;
switch ss
case 1
lfgauss; % Load flow solution by Gauss-Seidel method
case 2
decouple % Load flow solution by fast decoupled method
case 3
Lfnewton % Load flow solution by Newton-Raphson method
end
Busout; % Prints the power flow solution on the screen
Lineflow; % Computes and displays the line flow and losses
pp=[Pg(1);Pg(2);Pg(5);Pg(8);Pg(11);Pg(13)];
%find cost
F = zeros(6,1);
c = [0;0;0;0;0;0];
b = [2;1.75;1;3.25;3;3];
a = [0.00375;0.0175;0.0625;0.00834;0.02500;0.02500];
for i=1:6,
F(i)=(a(i)*pp(i)^2)+b(i)*pp(i)+c(i);
end
FT = sum(F);
% Gen1 constrain
if pp(1)<50|pp(1)>200
FT=FT+10000;
end
%line flow constrain
MVA_line=S_line;
if MVA_line(1)>130|MVA_line(2)>130|MVA_line(4)>65|MVA_line(8)>130|MVA_line(5)>130|MVA_line(6)>65|MVA_line(11)>90|...
MVA_line(14)>70|MVA_line(17)>130|MVA_line(18)>32|MVA_line(19)>65|MVA_line(20)>32|MVA_line(27)>65|MVA_line(28)>65|MVA_line(12)>65|...
MVA_line(37)>65|MVA_line(38)>32|MVA_line(39)>32|MVA_line(40)>32|MVA_line(43)>16|MVA_line(49)>16|MVA_line(46)>16|MVA_line(53)>16|...
MVA_line(55)>32|MVA_line(31)>32|MVA_line(32)>32|MVA_line(33)>32|MVA_line(34)>32|MVA_line(59)>32|MVA_line(47)>16|MVA_line(62)>16|...
MVA_line(64)>16|MVA_line(67)>16|MVA_line(69)>16|MVA_line(70)>16|MVA_line(76)>65|MVA_line(74)>16|MVA_line(75)>16|MVA_line(80)>16|MVA_line(25)>32|MVA_line(21)>32
FT=FT+10000;
end
Trm_loss=Transmissionloss;
%Line flow security
%line loading constrain
Trm_loss=Transmissionloss;
if Trm_loss>100
FT=FT+50*(Trm_loss-100);
end
% voltage contrain
for kk=1:15
if Vm(kk)>1.1|Vm(kk)<0.9
FT=FT+1000;
end
end