Issue
Pandapower does not follow the VDE0102 norm correctly in the min case for transformers. The impedance correction factor K_T should only be applied in the max case.
(See IEC 60909-0:2016 6.3.3)
Feature Checklist
Searched the issues page for similar reports
Read the relevant sections of the documentation
Browse the tutorials and tests for usefull code snippets and examples of use
Issue
Pandapower does not follow the VDE0102 norm correctly in the min case for transformers. The impedance correction factor K_T should only be applied in the max case.
(See IEC 60909-0:2016 6.3.3)
Pull request is here: #2168