[bug] Wrong usage of transformer impedance correction factor K_T in min case of short-circuit calculation #2384

Closed
3 of 4 tasks
envelio-cb opened this issue Aug 30, 2024 · 1 comment

Comments

@envelio-cb
Copy link

envelio-cb commented Aug 30, 2024

Feature Checklist

Issue

Pandapower does not follow the VDE0102 norm correctly in the min case for transformers. The impedance correction factor K_T should only be applied in the max case.
(See IEC 60909-0:2016 6.3.3)

Pull request is here: #2168

Label

  • Relevant labels are selected
@pawellytaev
Copy link
Contributor

pawellytaev commented Sep 4, 2024

Hi @envelio-cb, thanks for opening this issue and the PR. I'll close this here, so we can communicate on the PR #2168 directly