correct transformer x calculations #269

Open
ulfmueller opened this issue Jun 20, 2024 · 1 comment
Open

correct transformer x calculations #269

ulfmueller opened this issue Jun 20, 2024 · 1 comment
Assignees

Comments

@ulfmueller
Copy link
Member

ulfmueller commented Jun 20, 2024

in pypsa the transformer reactances are in p.u. values. But the base power is not 1 MVA as calculated internally for all other components but the transformer specific installed power (s_nom). Therefore I think we have to change this line accordingly to:
(br_x/100)*rate_a

Whereever else transformer are added to the system in powerd-data/egon-data or eTraGo we should check that it is handled the same.

@ClaraBuettner do you agree? Or did I get s.th. wrong?

@ulfmueller ulfmueller self-assigned this Jun 20, 2024
@ulfmueller
Copy link
Member Author

ulfmueller commented Jun 20, 2024

This 0c6c5ff tackles it - so it is part of PR #258