A new optional attribute ratedS
in TwoWindingsTransformer
and ThreeWindingsTransformer.Leg
has been introduced to model apparent power.
If ratedS
is not set to Double.NaN
, it should be strictly positive.
Shunt compensators can now be regulated. New attributes (regulation (boolean)
, targetV (double)
, targetDeadband (double)
and regulatingTerminal (Terminal)
) have been added to ShuntCompensator
and can be set and accessed. However, to serialize or deserialize a shunt compensator with any of these attributes with a non-default value, IIDM-XML version 1.1 must be used. Otherwise, the serialization and deserialization will fail.
To know more about these attributes and their default values, go to the documentation page of ShuntCompensator
.
fictitious
is now an optional boolean
attribute for every classes extending Identifiable
. For any Identifiable
, you can now use:
identifiable.setFictitious(true);
boolean fictitious = identifiable.isFictitious();
If you are using a custom implementation, be sure to implement this method in order not to throw an UnsupportedOperationException
.
This new method specifies if there is any electrical equipment, a switch or an internal connection attached to a given node in a voltage level.
If you are using a custom implementation, be sure to implement this method in order not to throw an UnsupportedOperationException
.
The attribute targetDeadband
in RatioTapChanger
and PhaseTapChanger
is now required if RatioTapChanger.regulating
is set to true
or PhaseTapChanger.regulationMode
is not set to FIXED_TAP
.
If targetDeadband
is not defined in these cases, an exception will be thrown. Hence, add the line:
tapChangerAdder.setTargetDeadband(0.0);
to keep the same behavior as before. Of course, you can also add another value if it is more appropriate to your use case. At any rate, in the cases described above, targetDeadband
should not be Double.NaN
.
The attribute nodeCount
in the nodeBreakerTopology
element has been deleted from this IIDM-XML version: it is not possible to pre-create vertices in the voltage level's graph in advance as this design was prone to allocation errors. Graph's vertices are created on the fly while attaching network components (a connectable equipment, a switch or an internal connection). When reading an IIDM-XML file in a prior version, the attribute nodeCount
will be ignored. When writing an IIDM-XML file in a prior version, the attribute nodeCount
will be written based on the number of vertices in the voltage level's graph.
The attribute lossFactor
in the LCC or VSC converter stations is not a ratio anymore but a percentage. In the previous version, there was no integrity test on its value, but since IIDM-XML v1.2, its value should be positive, and less than 100. We consider this as a breaking change because the results of a simulation could be different.